Monday, April 21, 2014

HVS - J In-Line Splice (15kV)

HVS - J (15 kV)

In-Line Splice For 1/C Jacketed Concentric Neutral Cables Rated for use at 15 Kilovolts

These pre-engineered Raychem HVS-J splice kits provide stress control, rebuild the shielding systems,
and restore primary cable insulation to 133% of the cable’s original insulation level.

In addition to the unique internal moisture seal, the SJ/EJ kits feature the MBSM wraparound
outer jacket which provides mechanical resistance to abrasion and impact, as well as an external
moisture seal.
  • High recovery forces
  • Same range as prior HVS-1510S-J
  • Range taking copper ShearBolt connector available




Labeled Reference



Commonly Supplied HVS-J Sizes Provided without Connector (see above image for reference)
HVS-C-1511S-J is supplied with an Insulation Diameter of 17 - 24 mm (A), a Jacket O.D. up to
30 mm (B). Maximum Connector Dimensions include an O.D. of 20 mm (C) and length of 100 mm (D).
The Kits Installed Length is 700 mm (L) with a Required Installation Space of 700 mm (M).

HVS-C-1512S-J is supplied with an Insulation Diameter of 23 - 33 mm (A), a Jacket O.D. up to
42 mm (B). Maximum Connector Dimensions include an O.D. of 30 mm (C) and length of 125 mm (D).
The Kits Installed Length is 700 mm (L) with a Required Installation Space of 700 mm (M).

HVS-C-1513S-J is supplied with an Insulation Diameter of 28 - 47 mm (A), a Jacket O.D. up to
48 mm (B). Maximum Connector Dimensions include an O.D. of 44 mm (C) and length of 150 mm (D).
The Kits Installed Length is 870 mm (L) with a Required Installation Space of 870 mm (M).

HVS-C-1514S-J is supplied with an Insulation Diameter of 33 - 48 mm (A), a Jacket O.D. up to
58 mm (B). Maximum Connector Dimensions include an O.D. of 47 mm (C) and length of 200 mm (D).
The Kits Installed Length is 870 mm (L) with a Required Installation Space of 870 mm (M).


Commonly Supplied HVS-J Sizes Provided with Copper Mechanical ShearBolt Connector 
(see above image for reference)
HVS-C-1512S-J-M1 is supplied with an Insulation Diameter of 23 - 33 mm (A), a Jacket O.D. up to
42 mm (B). Maximum Connector Dimensions include an O.D. of 30 mm (C) and length of 100 mm (D).
The Kits Installed Length is 700 mm (L) with a Required Installation Space of 700 mm (M).

HVS-C-1513S-J-M2 is supplied with an Insulation Diameter of 28 - 47 mm (A), a Jacket O.D. up to
48 mm (B). Maximum Connector Dimensions include an O.D. of 37 mm (C) and length of 125 mm (D).
The Kits Installed Length is 870 mm (L) with a Required Installation Space of 870 mm (M).

Commonly Supplied HVS-J Sizes Provided with Aluminum Mechanical ShearBolt Connector 
(see above image for reference)
HVS-S-1512S-J-M4 is supplied with an Insulation Diameter of 17 - 24 mm (A), a Jacket O.D. up to
30 mm (B). Maximum Connector Dimensions include an O.D. of 24 mm (C) and length of 65 mm (D).
The Kits Installed Length is 700 mm (L) with a Required Installation Space of 700 mm (M).

HVS-S-1512S-J-M5 is supplied with an Insulation Diameter of 20 - 30 mm (A), a Jacket O.D. up to
42 mm (B). Maximum Connector Dimensions include an O.D. of 30 mm (C) and length of 100 mm (D).
The Kits Installed Length is 700 mm (L) with a Required Installation Space of 700 mm (M).

HVS-S-1513S-J-M6 is supplied with an Insulation Diameter of 26 - 34 mm (A), a Jacket O.D. up to
45 mm (B). Maximum Connector Dimensions include an O.D. of 34 mm (C) and length of 125 mm (D).
The Kits Installed Length is 870 mm (L) with a Required Installation Space of 870 mm (M).

HVS-S-1542S-J-M8 is supplied with an Insulation Diameter of 29 - 39 mm (A), a Jacket O.D. up to
48 mm (B). Maximum Connector Dimensions include an O.D. of 40 mm (C) and length of 150 mm (D).
The Kits Installed Length is 870 mm (L) with a Required Installation Space of 870 mm (M).

HVS-S-1514S-J-M9 is supplied with an Insulation Diameter of 34 - 43 mm (A), a Jacket O.D. up to
58 mm (B). Maximum Connector Dimensions include an O.D. of 43 mm (C) and length of 200 mm (D).
The Kits Installed Length is 870 mm (L) with a Required Installation Space of 870 mm (M).














Raychem HVS-500/HVSA-500 splices for 1/C and 3/C Inline Cables

Raychem HVS-500/HVSA-500

Splices for 1/C and 3/C Inline Cable, Including Armored (5 kV Non-Shielded)

  • Non-shielded cable splices provide high abrasion-resistance and a positive environmental seal
  • Kits accommodate both jacketed and unjacketed cable
  • Rated to meet the applicable portions of IEEE 404














Common Sizes for 1/C Non-Shielded Power Cables (use left image for reference)
HVS-501 is supplied with an Insulation Diameter of 10 - 18 mm (A), a Jacket O.D. up to 20 mm (B).
Maximum Connector Dimensions include an O.D. of 17 mm (C) and length of 76 mm (D). The Kits
Installed Length is 254 mm (L) with a Required Installation Space of 559 mm (M).

HVS-502 is supplied with an Insulation Diameter of 17 - 27 mm (A), a Jacket O.D. up to 30 mm (B).
Maximum Connector Dimensions include an O.D. of 25 mm (C) and length of 102 mm (D). The Kits
Installed Length is 279 mm (L) with a Required Installation Space of 610 mm (M).

HVS-503 is supplied with an Insulation Diameter of 24-42 mm (A), a Jacket O.D. up to 47 mm (B).
Maximum Connector Dimensions include an O.D. of 47 mm (C) and length of 152 mm (D). The Kits
Installed Length is 381 mm (L) with a Required Installation Space of 762 mm (M).

Common Sizes for 3/C Non-Shielded Power Cables with No Armor (use right image for reference)
HVS-3-501 is supplied with an Insulation Diameter of 10 - 18 mm (A), a Jacket O.D. up to 76 mm (B).
Maximum Connector Dimensions include an O.D. of 17 mm (C) and length of 76 mm (D). The Kits
Installed Length is 812 mm (L) with a Required Installation Space of 1016 mm (M).

HVS-3-502 is supplied with an Insulation Diameter of 17 - 27 mm (A), a Jacket O.D. up to 76 mm (B).
Maximum Connector Dimensions include an O.D. of 25 mm (C) and length of 102 mm (D). The Kits
Installed Length is 1016 mm (L) with a Required Installation Space of 1219 mm (M).

HVS-3-503 is supplied with an Insulation Diameter of 24 - 42 mm (A), a Jacket O.D. up to 100 mm (B).
Maximum Connector Dimensions include an O.D. of 47 mm (C) and length of 152 mm (D). The Kits
Installed Length is 1219 mm (L) with a Required Installation Space of 1422 mm (M).

Common Sizes for 3/C Non-Shielded Power Cables with Armor (use right image for reference)
HVSA-3-501 is supplied with an Insulation Diameter of 10 - 18 mm (A), a Jacket O.D. up to 76 mm (B).
Maximum Connector Dimensions include an O.D. of 17 mm (C) and length of 76 mm (D). The Kits
Installed Length is 1016 mm (L) with a Required Installation Space of 1219 mm (M).

HVSA-3-502 is supplied with an Insulation Diameter of 17 - 27 mm (A), a Jacket O.D. up to 76 mm (B).
Maximum Connector Dimensions include an O.D. of 25 mm (C) and length of 102 mm (D). The Kits
Installed Length is 1016 mm (L) with a Required Installation Space of 1219 mm (M).

HVSA-3-503 is supplied with an Insulation Diameter of 24 - 42 mm (A), a Jacket O.D. up to 100 mm (B).
Maximum Connector Dimensions include an O.D. of 47 mm (C) and length of 152 mm (D). The Kits
Installed Length is 1321 mm (L) with a Required Installation Space of 1524 mm (M).

























Monday, March 31, 2014

Smart Limiter

Cable protectors for secondary cables


Smart Limiter

Cable Protection

Smart Limiter cable protectors helps to support higher operating temperatures of secondary cables. Many utilities, view network systems as the most attractive option for customers seeking steadfast reliability. The Smart Limiter cable protector will assist companies in rapidly restoring their network system to its most reliable state. When the limiters operate, they can be easily identified and replaced. Available in 3-way, 5-way and 7- way configurations and provides fast installation in compact spaces through the use of ShearBolt connectors. No special tools are required for installation, only 11/16" socket for installation and 1/2" for removal.

Smart Limiter Cable Protector Features and Benefits Include:

  • Increased reliability by protecting cable systems from damage due to fault current
  • Quick visual identification of blown limiters reduces the time needed to find faulted limiters
  • Sealing and mechanical protection are built in, eliminating the need for additional components
  • High-temperature clear inner and outer shells helping to heat
  • The limiter will only blow on secondary faults and effortlessly coordinate with network protector fuses
  • Minimal exposure to energized parts. Only the conductor being inserted into the limiter needs to be exposed making it very safe
  • Fuse operation is entirely contained in a ballistic enclosure
  • Smart Limiter Cable Protectors are 100% submersible
  • GelPort cable entries will quench any arc when "live" connections are made; making picking up load safer
  • Hinged bolt caps allow re-entry; enabling voltage measurements to be taken
  • Modular design allows circuits to be added or subtracted without cutting cables
  • Smart Limiter Cable Protectors are designed specifically for 208Y / 120V systems

Commonly used Smart Limiter Cable Protector Options
Smart Limiter Non-Fused splice for 4/0 cable
Smart Limiter Fused for 4/0 cable
Smart Non-Fused splice for 250 kcmil cable
Smart Fused limiter for 250 kcmil cable
Smart Non-Fused splice for 350 kcmil cable
Smart Fused limiter for 350 kcmil cable
Smart Non-Fused splice for 500 kcmil cable
Smart Fused limiter for 500 kcmil cable
Smart Non-Fused splice for 750 kcmil cable
Smart Fused limiter for 750 kcmil cable


Commonly used Crab Joint Sizes
3 way copper crab join with 4/0 conductors
5 way copper crab join with 4/0 conductors
7 way copper crab join with 4/0 conductors
3 way copper crab joint with 250 kcmil conductors
5 way copper crab joint with 250 kcmil conductors
7 way copper crab joint with 250 kcmil conductors
3 way copper crab joint with 350 kcmil conductors
5 way copper crab joint with 350 kcmil conductors
7 way copper crab joint with 350 kcmil conductors
3 way copper crab joint with 500 kcmil conductors
5 way copper crab joint with 500 kcmil conductors
7 way copper crab joint with 500 kcmil conductors
3 way copper crab joint with 750 kcmil conductors
5 way copper crab joint with 750 kcmil conductors
7 way copper crab joint with 750 kcmil conductors