Monday, April 21, 2014

CSJA JCN/EG; All-in-one Cold Shrinkable Joints


CSJA JCN/EG

In-Line Cold Shrinkable Joints Specifically for 1/C Jacketed Concentric Neutral Cables (15-35 kV)


TE’s Raychem “All-in-One” CSJA is a cold shrinkable joint for 15 kV through 35 kV. It is designed to
splice jacketed concentric neutral (JCN) cables.
  • Cable joint has a pre-expanded EPDM rejacketing sleeve and an integrated neutral sock.
    The “All-in-One” design is easy to install with minimal steps and short installation time
  • A pre-expanded, single-piece silicone rubber joint body with high mechanical expansion capability
    allows a wide application range
  • An ergonomically designed spiral holdout provides a smooth installation with low release forces.
  • Total length of the splice body on the holdout is 14 to 19 inches providing a compact design.
  • The Silicone rubber body provides high dielectric strength, high tear strength, low tension set, and
    excellent low temperature recovery
  • Integrated electrical stress control enhanced by factory molded stress cones and Faraday cage.
  • Void filling stress relief mastics are not necessary.
  • Proven shield continuity concept. The neutral wires are connected externally. The integrated pre-expanded neutral sock is connected to the neutral wires by a constant force spring. This provides
    the metallic shielding system to the cable joint.
  • The joint accepts both mechanical and compression connectors.
  • Meets IEEE-404 requirements for 15 kV through 35 kV.
 Each silicone splice body is factory tested to include AC withstand and partial discharge in
accordance with IEEE-404 production tests.







Selection Information:






 Commonly used CSJA JCN/EG Joints Without Connector

CSJA-JCN/EG-1511 is supplied with a Voltage Class of 15 kV and a Nominal Cable Range of #2-350. The Insulation O.D. range is 17.5-30.5 mm (A) with a Maximum Jacket O.D. of 38.1 mm (B). The Maximum Connector Dimensions include an O.D. of 33 mm (C) and a Length of 140 mm (D).

CSJA-JCN/EG-1512 is supplied with a Voltage Class of 15 kV and a Nominal Cable Range of 4/0-750. The Insulation O.D. range is 22.1-35.6 mm (A) with a Maximum Jacket O.D. of 46 mm (B). The Maximum Connector Dimensions include an O.D. of 38 mm (C) and a Length of 140 mm (D).

CSJA-JCN/EG-1513 is supplied with a Voltage Class of 15 kV and a Nominal Cable Range of 350-1000. The Insulation O.D. range is 26.2-40 mm (A) with a Maximum Jacket O.D. of 52.1 mm (B). The Maximum Connector Dimensions include an O.D. of 42 mm (C) and a Length of 170 mm (D).

CSJA-JCN/EG-1514 is supplied with a Voltage Class of 15 kV and a Nominal Cable Range of 750-1250. The Insulation O.D. range is 32.5-52 mm (A) with a Maximum Jacket O.D. of 66 mm (B). The Maximum Connector Dimensions include an O.D. of 47 mm (C) and a Length of 200 mm (D).

CSJA-JCN/EG-2812 is supplied with a Voltage Class of 28 kV and a Nominal Cable Range of #1-500. The Insulation O.D. range is 22.1-35.6 mm (A) with a Maximum Jacket O.D. of 46 mm (B). The Maximum Connector Dimensions include an O.D. of 38 mm (C) and a Length of 140 mm (D).

CSJA-JCN/EG-2813 is supplied with a Voltage Class of 28 kV and a Nominal Cable Range of 4/0-750. The Insulation O.D. range is 26.2-40 mm (A) with a Maximum Jacket O.D. of 52.1 mm (B). The Maximum Connector Dimensions include an O.D. of 42 mm (C) and a Length of 170 mm (D)

 CSJA-JCN/EG-2814 is supplied with a Voltage Class of 28 kV and a Nominal Cable Range of 500-1250. The Insulation O.D. range is 32.5-52 mm (A) with a Maximum Jacket O.D. of 66 mm (B). The Maximum Connector Dimensions include an O.D. of 47 mm (C) and a Length of 200 mm (D).

 CSJA-JCN/EG-3513 is supplied with a Voltage Class of 35 kV and a Nominal Cable Range of 1/0-350. The Insulation O.D. range is 26.2-37.8 mm (A) with a Maximum Jacket O.D. of 52.1 mm (B). The Maximum Connector Dimensions include an O.D. of 35.6 mm (C) and a Length of 140 mm (D).

CSJA-JCN/EG-3514 is supplied with a Voltage Class of 35 kV and a Nominal Cable Range of 350-1000. The Insulation O.D. range is 34.54-52 mm (A) with a Maximum Jacket O.D. of 66 mm (B). The Maximum Connector Dimensions include an O.D. of 50 mm (C) and a Length of 200 mm (D)

CSJA-JCN/EG-3515 is supplied with a Voltage Class of 35 kV and a Nominal Cable Range of 750-1250. The Insulation O.D. range is 41.4-60 mm (A) with a Maximum Jacket O.D. of 66 mm (B). The Maximum Connector Dimensions include an O.D. of 60 mm (C) and a Length of 200 mm (D)



Commonly used CSJA JCN/EG Joints with Copper Mechanical ShearBolt Connector

CSJA-JCN/EG-1511M1 is supplied with a Voltage Class of 15 kV and a Nominal Cable Range of 2/0-350. The Insulation O.D. range is 17.5-30.5 mm (A) with a Maximum Jacket O.D. of 38.1 mm (B). The Diameter Over Cable Conductor range is 9.5-18.7 mm.

CSJA-JCN/EG-1512M1 is supplied with a Voltage Class of 15 kV and a Nominal Cable Range of 4/0-500. The Insulation O.D. range is 22.1-35.6 mm (A) with a Maximum Jacket O.D. of 46 mm (B). The Diameter Over Cable Conductor range is 9.5-18.7 mm.

CSJA-JCN/EG-1512M2 is supplied with a Voltage Class of 15 kV and a Nominal Cable Range of 350-750. The Insulation O.D. range is 22.1-35.6 mm (A) with a Maximum Jacket O.D. of 46 mm (B). The Diameter Over Cable Conductor range is 14.5-24 mm.

CSJA-JCN/EG-1513M2 is supplied with a Voltage Class of 15 kV and a Nominal Cable Range of 350-750. The Insulation O.D. range is 26.2-40 mm (A) with a Maximum Jacket O.D. of 52.1 mm (B). The Diameter Over Cable Conductor range is 14.5-24 mm.

 CSJA-JCN/EG-2812M1 is supplied with a Voltage Class of 28 kV and a Nominal Cable Range of 2/0-500. The Insulation O.D. range is 22.1-35.6 mm (A) with a Maximum Jacket O.D. of 46 mm (B). The Diameter Over Cable Conductor range is 9.5-18.7 mm.

CSJA-JCN/EG-2813M2 is supplied with a Voltage Class of 28 kV and a Nominal Cable Range of 350-750. The Insulation O.D. range is 26.2-40 mm (A) with a Maximum Jacket O.D. of 52.1 mm (B). The Diameter Over Cable Conductor range is 14.5-24 mm.

CSJA-JCN/EG-2814M2 is supplied with a Voltage Class of 28 kV and a Nominal Cable Range of 500-750. The Insulation O.D. range is 26.2-40 mm (A) with a Maximum Jacket O.D. of 52.1 mm (B). The Diameter Over Cable Conductor range is 14.5-24 mm.

CSJA-JCN/EG-3513M1 is supplied with a Voltage Class of 35 kV and a Nominal Cable Range of 2/0-350. The Insulation O.D. range is 26.2-37.8 mm (A) with a Maximum Jacket O.D. of 52.1 mm (B). The Diameter Over Cable Conductor range is 9.5-18.7 mm.

CSJA-JCN/EG-3514M2 is supplied with a Voltage Class of 35 kV and a Nominal Cable Range of 350-750. The Insulation O.D. range is 34.54-52 mm (A) with a Maximum Jacket O.D. of 66 mm (B). The Diameter Over Cable Conductor range is 14.5-24 mm. 













































HVSH-MOD; H Configuration Kits


HVSH-MOD

H Configuration Kits for 1/C Shielded Power Cable (15 kV)


TE Connectivity’s Raychem HVSH-1520D-MOD and HVSH-1580D-MOD series modification
kits are used in conjunction with HVSY-1520S and HVSY-1580D-MOD series wye splice kits.
This combination provides a heat-shrinkable 15 kV system that accommodates “H-configuration”
connections for single-conductor power cables This kit will accom modate both crimped connectors
(copper conductor only) and soldered connectors.

These splices can be used for submersible or direct burial applications and have been tested to
meet the performance requirements of IEEE 404










HVSY Wye Splice Kit Options Paired with Appropriate HVSH-MOD in Order to make "H-Configuration" Rated for use at 15 kV


HVSY-1522S is supplied for a Main Poly Conductor Size ranging #2-4/0 with the Tap ranging the same size.The Insulation Diameter for the Main and Tap is a min. of 17 mm and a max. of 27 mm (A/E). The Max Connector Length is 75 mm (D). HVSY-1522S is to be paired with HVSH-1522-MOD to make an "H-configuration".

HVSY-1523S is supplied for a Main Poly Conductor Size ranging 250-750 with the Tap ranging #2-750.The Insulation Diameter for the Main has a min. of 24 mm and a max. of 37 mm (A). The Insulation Diameter for the Tap has a min. of 17 mm with a max. of 37 mm (E). The Max Connector Length is 
90 mm (D). HVSY-1523S is to be paired with HVSH-1523-MOD to make an "H-configuration".


HVSY-1582D is supplied for a PILC/poly Conductor Size with the Main and Tap ranging #2-4/0. The PILC/Poly Insulation Diameter for the Main and Tap have a Min.-Max. range of 17-27 mm (A/E). The Maximum Connector Length of 75 mm (D).HVSY-1582D is to be paired with HVSH-1582-MOD to make an "H-configuration".

HVSY-1583D is supplied for a PILC/poly Conductor Size with the Main ranging 250-750 and the tap ranging #2-750. The PILC/Poly Insulation Diameter for the Main has a Min.-Max. range of 24-37 mm (A) and 17-37 mm for the Tap (E). The Maximum Connector Length of 90 mm (D). HVSY-1583D is to be paired with HVSH-1583D-MOD to make an "H-configuration".

HVSY; Wye (Tap) Splice Kit


HVSY

Wye (Tap) Splices for 1/C Poly-Poy, PILC-PILC, and PILC-POLY Cable Rated for use at 15 kV

TE Connectivity’s Raychem Wye (Tap) splice kits may be used for submersible or direct burial
applications and have been tested to meet the performance requirements of IEEE-404. They include a
positive heat-activated sealant system that eliminates taping between main and tap cables.
  • Designed to seal against moisture ingress by including a branch clip and the heavy-duty MBSM
    wraparound sleeve
  • Internal moisture seals provide a redundant seal against water intrusion
  • Splices accept a wide range of main and tap cable sizes
  • Compact shape simplifies cable training
  • Rated to IEEE 404
HVSY-1520S is for use on copper tape, wire shield, lead sheath, and UniShield cables HVSY-1580D
is for use as a wye splice where the main and/or tap cables may be paper-insulated, lead-covered
(PILC) cable; varnished cambric-insulated, or lead-covered (VCLC) cable.





Selection Information:






Common HVSY (15 kV Polymeric Wye) For use with Soldered Connectors:
HVSY-1522S is supplied for a Main Poly Conductor Size ranging #2-4/0 with the Tap ranging the same size.The Insulation Diameter for the Main and Tap is a min. of 17 mm and a max. of 27 mm (A/E). The Max Connector Length is 75 mm (D).

HVSY-1523S is supplied for a Main Poly Conductor Size ranging 250-750 with the Tap ranging #2-750.The Insulation Diameter for the Main has a min. of 24 mm and a max. of 37 mm (A). The Insulation Diameter for the Tap has a min. of 17 mm with a max. of 37 mm (E). The Max Connector Length is 
90 mm (D).

Common HVSY (15 kV PILC and PILC-Poly Wye)
HVSY-1582D is supplied for a PILC/poly Conductor Size with the Main and Tap ranging #2-4/0. The PILC/Poly Insulation Diameter for the Main and Tap have a Min.-Max. range of 17-27 mm (A/E). The Lead Sheath O.D. Max. is 30 mm with a Maximum Connector Length of 75 mm (D).

HVSY-1583D is supplied for a PILC/poly Conductor Size with the Main ranging 250-750 and the tap ranging #2-750. The PILC/Poly Insulation Diameter for the Main has a Min.-Max. range of 24-37 mm (A) and 17-37 mm for the Tap (E). The Lead Sheath O.D. Max. is 38 mm with a Maximum Connector Length of 90 mm (D).