HVES Heat-Shrinkable Live End Seals

HVES

Heat-Shrinkable Live End Seal for 1/C PILC and Poly or 3/C PILC Cable (15-25 kV)

TE Connectivity’s Raychem HVES heat-shrinkable live end seals insulate and seal the ends of
polymeric and PILC cables. These kits consist of heat-shrinkable tubings and a high-dielectric
strength, polymeric plug which overlap the conductor to provide excellent insulation. The outer
adhesive-lined rejacketing sleeve is designed to provide a positive environmental seal.

Once the HVES kit is installed, the cable can be re-energized Typical applications include the live
ending of spare cables for future use, isolating a failed cable length, and sectionalizing a cable circuit during system maintenance and repair, expansion, or testing.

Selection Information:


Common HVES End Seal Sizes for 1/C PILC/VCLC and 1/C Poly Rated for use at 15 kV
HVES-1521D supplied for a PILC/Poly Conductor Size ranging from #4-4/0 with a PILC Min.-Max. Insulation Diameter of 15-23 mm (A) and a Poly Min.-Max. of 17-27 mm (A). The kits installed length is 305 mm (L).

HVES-1522D supplied for a PILC/Poly Conductor Size ranging from 250-350 with a PILC Min.-Max. Insulation Diameter of 22-28 mm (A) and a Poly Min.-Max. of 23-33 mm (A). The kits installed length is 305 mm (L).

HVES-1523D supplied for a PILC/Poly Conductor Size ranging from 500-750 with a PILC Min.-Max. Insulation Diameter of 27-33 mm (A) and a Poly Min.-Max. of 28-41 mm (A). The kits installed length is 305 mm (L).

HVES-1524D supplied for a PILC/Poly Conductor Size ranging from 750-1000 with a PILC Min.-Max. Insulation Diameter of 30-38 mm (A) and a Poly Min.-Max. of 32-46 mm (A). The kits installed length is 305 mm (L).


Common HVES End Seal Sizes for 1/C PILC/VCLC and 1/C Poly Rated for use at 25 kV
HVES-2521D supplied for a PILC/Poly Conductor Size ranging from #1-250 with a PILC Min.-Max. Insulation Diameter of 22-32 mm (A) and a Poly Min.-Max. of 22-32 mm (A). The kits installed length is 533 mm (L).

HVES-2522D supplied for a PILC/Poly Conductor Size ranging from 350-500 with a PILC Min.-Max. Insulation Diameter of 29-38 mm (A) and a Poly Min.-Max. of 29-38 mm (A). The kits installed length is 584 mm (L)

HVES-2523D supplied for a PILC/Poly Conductor Size ranging from 750-1000 with a PILC Min.-Max. Insulation Diameter of 38-48 mm (A) and a Poly Min.-Max. of 38-48 mm (A). The kits installed length is 635 mm (L)




Common HVES End Seal Sizes for 3/C PILC/VCLC Rated for use at 15 kV
HVES-3-1591 supplied for a PILC Conductor Size ranging from #4-4/0 with a PILC Min.-Max. Insulation Diameter of 15-25 mm (A). The kits installed length is 686 mm (L).

HVES-3-1592 supplied for a PILC Conductor Size ranging from 250-350 with a PILC Min.-Max. Insulation Diameter of 22-28 mm (A). The kits installed length is 686 mm (L).

HVES-3-1593 supplied for a PILC Conductor Size ranging from 500-750 with a PILC Min.-Max. Insulation Diameter of 27-38 mm (A). The kits installed length is 686 mm (L).

HVES-3-1594 supplied for a PILC Conductor Size ranging from 750-1000 with a PILC Min.-Max. Insulation Diameter of 29-44 mm (A). The kits installed length is 686 mm (L).


Common HVES End Seal Sizes for 3/C PILC/VCLC Rated for use at 25 kV 
HVES-3-2591E supplied for a PILC Conductor Size ranging from #1-250 with a PILC Min.-Max. Insulation Diameter of 22-30 mm (A). The kits installed length is 711 mm (L).

HVES-3-2592E supplied for a PILC Conductor Size ranging from 350-500 with a PILC Min.-Max. Insulation Diameter of 28-36 mm (A). The kits installed length is 787 mm (L).

HVES-3-2593E supplied for a PILC Conductor Size ranging from 750-1000 with a PILC Min.-Max. Insulation Diameter of 38-43 mm (A). The kits installed length is 813 mm (L).