Monday, April 21, 2014

HVS-C-1520S Heat Shrink Shielded Power Cable Splices

HVS-C-1520S

In-Line Splice for 1/C Shielded Cable (15 kV)

TE Connectivity’s Raychem heat-shrink shielded power cable splices feature a triple extrusion tube
which provides increased recovery forces, reduced shrinking time and improved profile conformity.
  • Reduced shrink time
  • Improved heat transfer
  • Significantly increased recovery forces
  • Reduced overall diameters and length
  • Optional copper ShearBolt connector available










HVS-C-1520S Splice for Compression Connector (connector not included)

HVC-C-1521S is supplied for a Conductor Size ranging #2-2/0. The Min.-Max. Insulation Diameter is 17-24 mm (A) and has a Maximum Jacket O.D. of 30 mm (B). The Maximum Connector O.D. is
20 mm (C) with a Maximum Connector Length of 100 mm (D).

HVC-C-1522S is supplied for a Conductor Size ranging 3/0-400. The Min.-Max. Insulation Diameter is 23-33 mm (A) and has a Maximum Jacket O.D. of 42 mm (B). The Maximum Connector O.D. is
30 mm (C) with a Maximum Connector Length of 125 mm (D).

HVC-C-1523S is supplied for a Conductor Size ranging 500-750. The Min.-Max. Insulation Diameter is 28-47 mm (A) and has a Maximum Jacket O.D. of 48 mm (B). The Maximum Connector O.D. is
44 mm (C) with a Maximum Connector Length of 150 mm (D).

HVC-C-1524S is supplied for a Conductor Size ranging 750-1000. The Min.-Max. Insulation Diameter is 33-48 mm (A) and has a Maximum Jacket O.D. of 58 mm (B). The Maximum Connector O.D. is
47 mm (C) with a Maximum Connector Length of 200 mm (D).



HVS-C-1520S with Copper ShearBolt (connector included)

HVS-C-1522S-M1 is supplied for a Conductor Size ranging 3/0-400. The Min.-Max. Insulation Diameter is 23-33 mm (A) and has a Maximum Jacket O.D. of 30 mm (B). The Maximum Connector O.D. is
30 mm (C) with a Maximum Connector Length of 100 mm (D).

HVS-C-1523S-M2 is supplied for a Conductor Size ranging 500-750. The Min.-Max. Insulation Diameter is 28-47 mm (A) and has a Maximum Jacket O.D. of 47 mm (B). The Maximum Connector O.D. is
37 mm (C) with a Maximum Connector Length of 125 mm (D).




Raychem HVS-500/HVSA-500 splices for 1/C and 3/C Inline Cables

Raychem HVS-500/HVSA-500

Splices for 1/C and 3/C Inline Cable, Including Armored (5 kV Non-Shielded)

  • Non-shielded cable splices provide high abrasion-resistance and a positive environmental seal
  • Kits accommodate both jacketed and unjacketed cable
  • Rated to meet the applicable portions of IEEE 404














Common Sizes for 1/C Non-Shielded Power Cables (use left image for reference)
HVS-501 is supplied with an Insulation Diameter of 10 - 18 mm (A), a Jacket O.D. up to 20 mm (B).
Maximum Connector Dimensions include an O.D. of 17 mm (C) and length of 76 mm (D). The Kits
Installed Length is 254 mm (L) with a Required Installation Space of 559 mm (M).

HVS-502 is supplied with an Insulation Diameter of 17 - 27 mm (A), a Jacket O.D. up to 30 mm (B).
Maximum Connector Dimensions include an O.D. of 25 mm (C) and length of 102 mm (D). The Kits
Installed Length is 279 mm (L) with a Required Installation Space of 610 mm (M).

HVS-503 is supplied with an Insulation Diameter of 24-42 mm (A), a Jacket O.D. up to 47 mm (B).
Maximum Connector Dimensions include an O.D. of 47 mm (C) and length of 152 mm (D). The Kits
Installed Length is 381 mm (L) with a Required Installation Space of 762 mm (M).

Common Sizes for 3/C Non-Shielded Power Cables with No Armor (use right image for reference)
HVS-3-501 is supplied with an Insulation Diameter of 10 - 18 mm (A), a Jacket O.D. up to 76 mm (B).
Maximum Connector Dimensions include an O.D. of 17 mm (C) and length of 76 mm (D). The Kits
Installed Length is 812 mm (L) with a Required Installation Space of 1016 mm (M).

HVS-3-502 is supplied with an Insulation Diameter of 17 - 27 mm (A), a Jacket O.D. up to 76 mm (B).
Maximum Connector Dimensions include an O.D. of 25 mm (C) and length of 102 mm (D). The Kits
Installed Length is 1016 mm (L) with a Required Installation Space of 1219 mm (M).

HVS-3-503 is supplied with an Insulation Diameter of 24 - 42 mm (A), a Jacket O.D. up to 100 mm (B).
Maximum Connector Dimensions include an O.D. of 47 mm (C) and length of 152 mm (D). The Kits
Installed Length is 1219 mm (L) with a Required Installation Space of 1422 mm (M).

Common Sizes for 3/C Non-Shielded Power Cables with Armor (use right image for reference)
HVSA-3-501 is supplied with an Insulation Diameter of 10 - 18 mm (A), a Jacket O.D. up to 76 mm (B).
Maximum Connector Dimensions include an O.D. of 17 mm (C) and length of 76 mm (D). The Kits
Installed Length is 1016 mm (L) with a Required Installation Space of 1219 mm (M).

HVSA-3-502 is supplied with an Insulation Diameter of 17 - 27 mm (A), a Jacket O.D. up to 76 mm (B).
Maximum Connector Dimensions include an O.D. of 25 mm (C) and length of 102 mm (D). The Kits
Installed Length is 1016 mm (L) with a Required Installation Space of 1219 mm (M).

HVSA-3-503 is supplied with an Insulation Diameter of 24 - 42 mm (A), a Jacket O.D. up to 100 mm (B).
Maximum Connector Dimensions include an O.D. of 47 mm (C) and length of 152 mm (D). The Kits
Installed Length is 1321 mm (L) with a Required Installation Space of 1524 mm (M).