Contact Us

We are Elite Distributors for Raychem / Tyco Electronics and
Master Distributors for Covalence Heat Shrink Sleeves
Call: 936/321-3333
Email: Stacey@jsicoatings.com or Steve@jsicoatings.com
Visit our official site: www.heatshrinksleeves.com
Pipeline Blog: blog.heatshrinksleeves.com
Showing posts with label dead break stand off plug. Show all posts
Showing posts with label dead break stand off plug. Show all posts

Monday, April 21, 2014

Deadbreak Standoff Plug; 600 Amp

Deadbreak Standoff Plug

600 Amp Rated for use Ranging from 15 kV up to 35 kV

Raychem 600A deadbreak standoff plug is available in both 15/28 kV and 35 kV Class versions.
The standoff plug is meant for use in a parking stand of an apparatus or junction, where it provides
insulated protection for energized 15/28-35 kV deadbreak interfaces.

They are frequently used temporarily or permanently within padmount cabinets, underground vaults,
switchgear, transformers, and a variety of other apparatus. Typical applications include isolating and
sectionalizing energized cable, system maintenance, circuit reconfiguration, and future expansion.

A fully shielded, submersible connection is offered, with conformance to IEEE Standard 386. These
standoff plugs are therefore interchangeable with other manufacturers’ products that also comply with
this standard.
  •  15/28 kV or 35 kV, 600A ratings
  • Designed to be installed in the parking stand of apparatus
  • Fully-shielded, fully submersible connection
  • Stainless steel eyebolt with a stainless steel pressure foot
  • Body bolted to stainless steel base bracket
  • Compatible with 900A, all copper circuits
  • Conforms to ANSI/IEEE standard 386




 15/28 kV Deadbreak Standoff Plug Ratings:
Voltage Class: 15/28 kV
Max Rating Phase-to-Ground: 16.2 kV
Max Rating Phase-to-Phase: 28 kV
AC 1 minute withstand: 45 kV
DC 15 minute withstand: 88 kV
BIL and full wave crest: 140 kV
Minimum Corona Level: 21.5 kV (3pC)
Continuous: 600A rms
24 Hour Overload: 1,000A rms

 35 kV Deadbreak Standoff Plug Ratings:
Voltage Class: 35 kV
Max Rating Phase-to-Ground: 21.1 kV
Max Rating Phase-to-Phase: 36.6 kV
AC 1 minute withstand: 50 kV
DC 15 minute withstand: 103 kV
BIL and full wave crest: 150 kV
Minimum Corona Level: 26 kV (3pC)
Continuous: 600A rms
24 Hour Overload: 1,000A rms