Contact Us

We are Elite Distributors for Raychem / Tyco Electronics and
Master Distributors for Covalence Heat Shrink Sleeves
Call: 936/321-3333
Email: Stacey@jsicoatings.com or Steve@jsicoatings.com
Visit our official site: www.heatshrinksleeves.com
Pipeline Blog: blog.heatshrinksleeves.com

Monday, April 21, 2014

Deadbreak Standoff Plug; 600 Amp

Deadbreak Standoff Plug

600 Amp Rated for use Ranging from 15 kV up to 35 kV

Raychem 600A deadbreak standoff plug is available in both 15/28 kV and 35 kV Class versions.
The standoff plug is meant for use in a parking stand of an apparatus or junction, where it provides
insulated protection for energized 15/28-35 kV deadbreak interfaces.

They are frequently used temporarily or permanently within padmount cabinets, underground vaults,
switchgear, transformers, and a variety of other apparatus. Typical applications include isolating and
sectionalizing energized cable, system maintenance, circuit reconfiguration, and future expansion.

A fully shielded, submersible connection is offered, with conformance to IEEE Standard 386. These
standoff plugs are therefore interchangeable with other manufacturers’ products that also comply with
this standard.
  •  15/28 kV or 35 kV, 600A ratings
  • Designed to be installed in the parking stand of apparatus
  • Fully-shielded, fully submersible connection
  • Stainless steel eyebolt with a stainless steel pressure foot
  • Body bolted to stainless steel base bracket
  • Compatible with 900A, all copper circuits
  • Conforms to ANSI/IEEE standard 386




 15/28 kV Deadbreak Standoff Plug Ratings:
Voltage Class: 15/28 kV
Max Rating Phase-to-Ground: 16.2 kV
Max Rating Phase-to-Phase: 28 kV
AC 1 minute withstand: 45 kV
DC 15 minute withstand: 88 kV
BIL and full wave crest: 140 kV
Minimum Corona Level: 21.5 kV (3pC)
Continuous: 600A rms
24 Hour Overload: 1,000A rms

 35 kV Deadbreak Standoff Plug Ratings:
Voltage Class: 35 kV
Max Rating Phase-to-Ground: 21.1 kV
Max Rating Phase-to-Phase: 36.6 kV
AC 1 minute withstand: 50 kV
DC 15 minute withstand: 103 kV
BIL and full wave crest: 150 kV
Minimum Corona Level: 26 kV (3pC)
Continuous: 600A rms
24 Hour Overload: 1,000A rms