Contact Us

We are Elite Distributors for Raychem / Tyco Electronics and
Master Distributors for Covalence Heat Shrink Sleeves
Call: 936/321-3333
Email: Stacey@jsicoatings.com or Steve@jsicoatings.com
Visit our official site: www.heatshrinksleeves.com
Pipeline Blog: blog.heatshrinksleeves.com

Monday, April 21, 2014

HVS Metal Laminated Wraparound Rejacketing Sleeve (25-35 kV)


HVS Metal Laminated Wraparound Rejacketing Sleeve

Splice Kits for 1/C LC and Flat Strap Shield Cable (25-35 kV)


The Raychem HVS kits feature a metal laminated wraparound rejacketing sleeve that reduces
moisture-vapor transmission. This tough sleeve also protects the splice from coincidental abrasion,
back fill, and handling damage.

Ground connections are made using stainless steel clamps and tinned copper braid. The ground
connections have been tested to multiple reclosed faults in excess of 13-kA rms without damage.
  • Designed to withstand fault current duty of 10-kA rms for 10 cycles
  • Rated to IEEE 404








Common HVS Options:


Rated for use at 25 kV

HVS-2531-LC is supplied for a Conductor Size ranging #1-250 and has a Min.-Max Insulation Diameter of
16-24 mm (A). The Maximum Jacket O.D. is 39 mm (B) with a Maximum Connector O.D. of 28 mm (C) and Maximum Connector Length of 102 mm (D).

HVS-2532-LC is supplied for a Conductor Size ranging 350-500 and has a Min.-Max Insulation Diameter of 30-38 mm (A). The Maximum Jacket O.D. is 50 mm (B) with a Maximum Connector O.D. of 
34 mm (C) and Maximum Connector Length of 152 mm (D).

HVS-2533-LC is supplied for a Conductor Size ranging 7501000 and has a Min.-Max Insulation Diameter of 38-46 mm (A). The Maximum Jacket O.D. is 61 mm (B) with a Maximum Connector O.D. of 
47 mm (C) and Maximum Connector Length of 203 mm (D).



Rated for use at 35 kV

HVS-3531-LC is supplied for a Conductor Size ranging 1/0-3/0 and has a Min.-Max Insulation Diameter of
29-34 mm (A). The Maximum Jacket O.D. is 39 mm (B) with a Maximum Connector O.D. of 25 mm (C) and Maximum Connector Length of 102 mm (D).

HVS-3532-LC is supplied for a Conductor Size ranging 4/0-500 and has a Min.-Max Insulation Diameter of 33-43 mm (A). The Maximum Jacket O.D. is 53 mm (B) with a Maximum Connector O.D. of 
41 mm (C) and Maximum Connector Length of 140 mm (D).

HVS-3533-LC is supplied for a Conductor Size ranging 750-1000 and has a Min.-Max Insulation Diameter of 42-55 mm (A). The Maximum Jacket O.D. is 71 mm (B) with a Maximum Connector O.D. of 
47 mm (C) and Maximum Connector Length of 203 mm (D).



















No comments:

Post a Comment