Contact Us

We are Elite Distributors for Raychem / Tyco Electronics and
Master Distributors for Covalence Heat Shrink Sleeves
Call: 936/321-3333
Email: Stacey@jsicoatings.com or Steve@jsicoatings.com
Visit our official site: www.heatshrinksleeves.com
Pipeline Blog: blog.heatshrinksleeves.com

Monday, April 21, 2014

Raychem HVS-500/HVSA-500 splices for 1/C and 3/C Inline Cables

Raychem HVS-500/HVSA-500

Splices for 1/C and 3/C Inline Cable, Including Armored (5 kV Non-Shielded)

  • Non-shielded cable splices provide high abrasion-resistance and a positive environmental seal
  • Kits accommodate both jacketed and unjacketed cable
  • Rated to meet the applicable portions of IEEE 404














Common Sizes for 1/C Non-Shielded Power Cables (use left image for reference)
HVS-501 is supplied with an Insulation Diameter of 10 - 18 mm (A), a Jacket O.D. up to 20 mm (B).
Maximum Connector Dimensions include an O.D. of 17 mm (C) and length of 76 mm (D). The Kits
Installed Length is 254 mm (L) with a Required Installation Space of 559 mm (M).

HVS-502 is supplied with an Insulation Diameter of 17 - 27 mm (A), a Jacket O.D. up to 30 mm (B).
Maximum Connector Dimensions include an O.D. of 25 mm (C) and length of 102 mm (D). The Kits
Installed Length is 279 mm (L) with a Required Installation Space of 610 mm (M).

HVS-503 is supplied with an Insulation Diameter of 24-42 mm (A), a Jacket O.D. up to 47 mm (B).
Maximum Connector Dimensions include an O.D. of 47 mm (C) and length of 152 mm (D). The Kits
Installed Length is 381 mm (L) with a Required Installation Space of 762 mm (M).

Common Sizes for 3/C Non-Shielded Power Cables with No Armor (use right image for reference)
HVS-3-501 is supplied with an Insulation Diameter of 10 - 18 mm (A), a Jacket O.D. up to 76 mm (B).
Maximum Connector Dimensions include an O.D. of 17 mm (C) and length of 76 mm (D). The Kits
Installed Length is 812 mm (L) with a Required Installation Space of 1016 mm (M).

HVS-3-502 is supplied with an Insulation Diameter of 17 - 27 mm (A), a Jacket O.D. up to 76 mm (B).
Maximum Connector Dimensions include an O.D. of 25 mm (C) and length of 102 mm (D). The Kits
Installed Length is 1016 mm (L) with a Required Installation Space of 1219 mm (M).

HVS-3-503 is supplied with an Insulation Diameter of 24 - 42 mm (A), a Jacket O.D. up to 100 mm (B).
Maximum Connector Dimensions include an O.D. of 47 mm (C) and length of 152 mm (D). The Kits
Installed Length is 1219 mm (L) with a Required Installation Space of 1422 mm (M).

Common Sizes for 3/C Non-Shielded Power Cables with Armor (use right image for reference)
HVSA-3-501 is supplied with an Insulation Diameter of 10 - 18 mm (A), a Jacket O.D. up to 76 mm (B).
Maximum Connector Dimensions include an O.D. of 17 mm (C) and length of 76 mm (D). The Kits
Installed Length is 1016 mm (L) with a Required Installation Space of 1219 mm (M).

HVSA-3-502 is supplied with an Insulation Diameter of 17 - 27 mm (A), a Jacket O.D. up to 76 mm (B).
Maximum Connector Dimensions include an O.D. of 25 mm (C) and length of 102 mm (D). The Kits
Installed Length is 1016 mm (L) with a Required Installation Space of 1219 mm (M).

HVSA-3-503 is supplied with an Insulation Diameter of 24 - 42 mm (A), a Jacket O.D. up to 100 mm (B).
Maximum Connector Dimensions include an O.D. of 47 mm (C) and length of 152 mm (D). The Kits
Installed Length is 1321 mm (L) with a Required Installation Space of 1524 mm (M).

























No comments:

Post a Comment