HVSY
Wye (Tap) Splices for 1/C Poly-Poy, PILC-PILC, and PILC-POLY Cable Rated for use at 15 kV
TE Connectivity’s Raychem Wye (Tap) splice kits may be used for submersible or direct burial
applications and have been tested to meet the performance requirements of IEEE-404. They include a
positive heat-activated sealant system that eliminates taping between main and tap cables.
applications and have been tested to meet the performance requirements of IEEE-404. They include a
positive heat-activated sealant system that eliminates taping between main and tap cables.
- Designed to seal against moisture ingress by including a branch clip and the heavy-duty MBSM
wraparound sleeve - Internal moisture seals provide a redundant seal against water intrusion
- Splices accept a wide range of main and tap cable sizes
- Compact shape simplifies cable training
- Rated to IEEE 404
is for use as a wye splice where the main and/or tap cables may be paper-insulated, lead-covered
(PILC) cable; varnished cambric-insulated, or lead-covered (VCLC) cable.
Common HVSY (15 kV Polymeric Wye) For use with Soldered Connectors:
HVSY-1522S is supplied for a Main Poly Conductor Size ranging #2-4/0 with the Tap ranging the same size.The Insulation Diameter for the Main and Tap is a min. of 17 mm and a max. of 27 mm (A/E). The Max Connector Length is 75 mm (D).
HVSY-1523S is supplied for a Main Poly Conductor Size ranging 250-750 with the Tap ranging #2-750.The Insulation Diameter for the Main has a min. of 24 mm and a max. of 37 mm (A). The Insulation Diameter for the Tap has a min. of 17 mm with a max. of 37 mm (E). The Max Connector Length is
90 mm (D).
Common HVSY (15 kV PILC and PILC-Poly Wye)
HVSY-1582D is supplied for a PILC/poly Conductor Size with the Main and Tap ranging #2-4/0. The PILC/Poly Insulation Diameter for the Main and Tap have a Min.-Max. range of 17-27 mm (A/E). The Lead Sheath O.D. Max. is 30 mm with a Maximum Connector Length of 75 mm (D).
HVSY-1583D is supplied for a PILC/poly Conductor Size with the
Main ranging 250-750 and the tap ranging #2-750. The PILC/Poly Insulation Diameter for the
Main has a Min.-Max. range of 24-37 mm (A) and 17-37 mm for the Tap (E). The Lead Sheath O.D. Max. is 38 mm with a Maximum Connector Length of 90 mm (D).
No comments: