Contact Us

We are Elite Distributors for Raychem / Tyco Electronics and
Master Distributors for Covalence Heat Shrink Sleeves
Call: 936/321-3333
Email: Stacey@jsicoatings.com or Steve@jsicoatings.com
Visit our official site: www.heatshrinksleeves.com
Pipeline Blog: blog.heatshrinksleeves.com

Monday, April 21, 2014

HVS - J In-Line Splice (25-35 kV)

HVS-J (25-35 kV)

In-Line Splice for 1/C Jacketed Concentric Neutral Cables rated for use at 25-35 kilovolts

These pre-engineered Raychem HVS-J splice kits provide stress control, rebuild the shielding systems,
and restore primary cable insulation to 133% of the cable’s original insulation level.

In addition to the unique internal moisture seal, the SJ/EJ kits feature the MBSM wraparound
outer jacket which provides mechanical resistance to abrasion and impact, as well as an external
moisture seal.
  • High recovery forces
  • Range taking copper ShearBolt connector available




Labeled Reference for Common HVS-J sizes





Commonly Supplied HVS-J (25-28 kV) Sizes (see above image for letter reference)
HVS-2511E-J is supplied with an Insulation Diameter of 23 - 30 mm (A), a Jacket O.D. up to
39 mm (B). Maximum Connector Dimensions include an O.D. of 28 mm (C) and length of 102 mm (D).
The Kits Installed Length is 1016 mm (L) with a Required Installation Space of 1422 mm (M).

HVS-2512E-J is supplied with an Insulation Diameter of 30 - 38 mm (A), a Jacket O.D. up to
50 mm (B). Maximum Connector Dimensions include an O.D. of 34 mm (C) and length of 152 mm (D).
The Kits Installed Length is 1219 mm (L) with a Required Installation Space of 1727 mm (M).

HVS-2513E-J is supplied with an Insulation Diameter of 38 - 46 mm (A), a Jacket O.D. up to
61 mm (B). Maximum Connector Dimensions include an O.D. of 47 mm (C) and length of 203 mm (D).
The Kits Installed Length is 1219 mm (L) with a Required Installation Space of 1778 mm (M)
Commonly Supplied HVS-J (35 kV) Sizes (see above image for letter reference)
HVS-3511S-J is supplied with an Insulation Diameter of 24 - 34 mm (A), a Jacket O.D. up to
39 mm (B). Maximum Connector Dimensions include an O.D. of 25 mm (C) and length of 127 mm (D).
The Kits Installed Length is 1118 mm (L) with a Required Installation Space of 1346 mm (M).

HVS-3512S-J is supplied with an Insulation Diameter of 30 - 43 mm (A), a Jacket O.D. up to
53 mm (B). Maximum Connector Dimensions include an O.D. of 41 mm (C) and length of 203 mm (D).
The Kits Installed Length is 1219 mm (L) with a Required Installation Space of 1600 mm (M).

HVS-3513S-J is supplied with an Insulation Diameter of 39 - 55 mm (A), a Jacket O.D. up to
71 mm (B). Maximum Connector Dimensions include an O.D. of 47 mm (C) and length of 254 mm (D).
The Kits Installed Length is 1219 mm (L) with a Required Installation Space of 1626 mm (M).






No comments: