HVS Wraparound Rejacketing Sleeve
1/C LC Shielded and Flat Strap Cables
TE Connectivity’s Raychem Rayfit HVS kits feature a metal laminated wraparound rejacketing
sleeve that reduces moisture-vapor transmission. This tough sleeve also protects the splice from
coincidental abrasion, back fill and handling damage.
sleeve that reduces moisture-vapor transmission. This tough sleeve also protects the splice from
coincidental abrasion, back fill and handling damage.
Ground connections are made using heavy duty stainless steel spring clamps and tinned copper
braid. The ground connections have been tested to multiple reclosed faults in excess of 13-kA rms
without damage.
- Designed to withstand fault current duty of 10-kA rms for 100 cycles
- Rated to IEEE 404
- For use on LC shield cable
Standard HVS-C-1530S Options without Connector
HVS-C-1531S is supplied for a Conductor Size ranging #2-2/0 and has a Min.-Max Insulation Diameter of 17-24 mm (A). The Maximum Jacket O.D. is 30 mm (B) with a Maximum Connector O.D. of 20 mm (C) and Maximum Connector Length of 100 mm (D).
HVS-C-1532S is supplied for a Conductor Size ranging 3/0-400 and has a Min.-Max Insulation Diameter of 23-33 mm (A). The Maximum Jacket O.D. is 42 mm (B) with a Maximum Connector O.D. of 30 mm (C) and Maximum Connector Length of 125 mm (D).
HVS-C-1533S is supplied for a Conductor Size ranging 500-750 and has a Min.-Max Insulation Diameter of 28-47 mm (A). The Maximum Jacket O.D. is 48 mm (B) with a Maximum Connector O.D. of
44 mm (C) and Maximum Connector Length of 150 mm (D).
HVS-C-1534S is supplied for a Conductor Size ranging 750-1000 and has a Min.-Max Insulation Diameter of 33-48 mm (A). The Maximum Jacket O.D. is 58 mm (B) with a Maximum Connector O.D. of
47 mm (C) and Maximum Connector Length of 200 mm (D).
Standard HVS-C-1530S Options with Copper Mechanical ShearBolt Connector
HVS-C-1532S-M1 is supplied for a Conductor Size ranging 3/0-400 and has a Min.-Max Insulation Diameter of 23-33 mm (A). The Maximum Jacket O.D. is 30 mm (B) with a Maximum Connector O.D. of 30 mm (C) and Maximum Connector Length of 100 mm (D).
HVS-C-1533S-M2 is supplied for a Conductor Size ranging 500-750 and has a Min.-Max Insulation Diameter of 28-47 mm (A). The Maximum Jacket O.D. is 47 mm (B) with a Maximum Connector O.D. of 37 mm (C) and Maximum Connector Length of 125 mm (D).
Standard HVS-C-1530S Options with Aluminum Mechanical ShearBolt Connector
HVS-C-1532S-M4 is supplied for a Conductor Size ranging #2-2/0 and has a Min.-Max Insulation Diameter of 17-24 mm (A). The Maximum Jacket O.D. is 30 mm (B) with a Maximum Connector O.D. of 24 mm (C) and Maximum Connector Length of 65 mm (D).
HVS-C-1532S-M5 is supplied for a Conductor Size ranging 2/0-350 and has a Min.-Max Insulation Diameter of 20-30 mm (A). The Maximum Jacket O.D. is 42 mm (B) with a Maximum Connector O.D. of 30 mm (C) and Maximum Connector Length of 100 mm (D).
HVS-C-1533S-M6 is supplied for a Conductor Size ranging 350-500 and has a Min.-Max Insulation Diameter of 26-34 mm (A). The Maximum Jacket O.D. is 45 mm (B) with a Maximum Connector O.D. of 34 mm (C) and Maximum Connector Length of 125 mm (D).
HVS-C-1534S-M8 is supplied for a Conductor Size ranging 500-750 and has a Min.-Max Insulation Diameter of 29-39 mm (A). The Maximum Jacket O.D. is 48 mm (B) with a Maximum Connector O.D. of 40 mm (C) and Maximum Connector Length of 150 mm (D).
HVS-C-1534S-M9 is supplied for a Conductor Size ranging 750-1000 and has a Min.-Max Insulation Diameter of 34-43 mm (A). The Maximum Jacket O.D. is 58 mm (B) with a Maximum Connector O.D. of 43 mm (C) and Maximum Connector Length of 200 mm (D).
No comments:
Post a Comment